LDS-6/UHF
Applications
? The LDS-6/UHF is a state-of- the-art, portable digital measuring system for the UHF processing of partial discharges acquired from installed GIS sensors, or UHF sensors. It combines the features of a PD detector and spectrum analyzer.
? PD quality tests on GIS using installed GIS sensors
? PD testing on HV Apparatus, using UHF technology
? Designed for on-site PD diagnosis tests as well as for manufacturing and research
? Single channel or Dual channel
? Available in 19" housing with external PC connected via Ethernet, or portable case with built in mini PC
Benefits
? Continuous UHF PD pulse processing
? Frequency selective PD measuring to eliminate noise
? Spectrum analyzer function
? PD pattern recognition
? Additional statistical evaluations
? Additional diagnosis tools for PD failure recognition and identification Specifications
? computer-aided measuring, recording, storing, monitoring and analysis (PRPDA) of PD pulses
? frequency domain signal conditioning
? software switch-able sensor amplifier for high sensitivity
? signal processing band width (FULL SPAN) 110 MHz to 1700 MHz
? Frequency selective measurement, resolution bandwidth (RBW) 7 MHz
? IF signal processing – 1.IF = 479 MHz / 2. IF = 36 MHz
? IF signal output 36 MHz, output impedance 50 Ohm
? PD measuring range up to 700mV attenuation in 2dB steps up to 62dB
? Software SPAN setup
? Spectrum analyzer function
? Software controlled 62 dB attenuation, 2 dB steps
? N – type signal input connector
? Protocol generator for creating customer specific test reports (optional available)
? Ethernet connection between measuring system and computer (only in 19" housing)
? with protective carry case for on-site applications
? housing 200 x 440 x 540 (H x W x D) with handle
? weight 18 kg
? The LDS-6/UHF (19" housing version) can be equipped with a wide-band unit for PD measurements acc. to IEC 60270
Accessories
LDS-6/UHF
? Active UHF-PD Sensor DN50 - For decoupling of electromagnetic PD signals from the inner of an oilpaper insulated transformers
? Active UHF-PD Sensor DN80 - For decoupling of electromagnetic PD signals from the inner of an oilpaper insulated transformers
? PD-Sensor Typ A - inductive line coupler, ungrounded type
? LDC-7/UHF - External Calibrator for functional check of the complete UHF PD detection circuit, only for UHF version of LDS-6
? UHF-connecting cables to connect the measuring device with the UHF sensor, length 20 m (2 pieces)
Additional Pictures